As of the time we first worked on this system we found that the
motor starter for the cooling tower roof blower is burned up and been bypassed.
The starter being bypassed causes the fan to run 24 hours a day
whenever the power is applied to the circuit.
To repair the starter it will be necessary to replace the entire
starter because the old one uses parts that are no longer available.
I have donated a starter box to Crain Hwy. that requires
that the contactor or coil be changed from 120 volts ac to 208-240 volts
ac. The overload heaters will also have to be changed to the correct current
rating to property protect the motor (replaced fall 1999 due to burnout
caused by wiring to 460-480 instead of 208-230). This caused a "slow
burn".
· Cost of replacement coil. $60.00
· Cost of new overload heaters. $30.00
· Cost to replace starter box, overloads and connect all wiring
to new box. $100.00
· Total $180.00 due upon testing of fan operation. and verification
of motor overloads.