How Furnace Fans and Blowers Work
I get many inquiries about Furnace Blowers
and fans and how they work.
For definitions see below. For the purposes of this text
I will use the word fan and blower interchangeably.
Most older gas furnaces that
have standing pilot systems and most oil hot air furnaces use a thermostat
switch located in the hot air plenum that detects when the furnace is hot
and turns on the blower. These thermostats (more commonly called the Fan/Limit
control) are usually made by honeywell or white-rodgers (Shown
below). The typical settings for the stops are 70 to 90 "Off", 130
to 150 "On", and the "Limit" to the bottom of the slot (lowest setting)
as long as you don't get nuisance shutting off of the fire. As you might
guess they also control the gas valve or oil burner if the furnace gets
too hot. If you have problems with the blower not shutting off, set the
"Off" setting to the bottom then after the burner cycles wait about 3 to
4 minutes and hold the dial and raise the stop until it shuts off. Run
the burner several more cycles to make sure it works reliably (use your
best judgment). If you have to replace one of these you will have to measure
the length of the probe that extends into the plenum. There are controls
made that are just a flush disk that extends into a
hole about 1 inch in diameter. These are necessary when the heat exchanger
makes it difficult to use a conventional limit.
Image of Conventional Fan/Limit made by Honeywell (Robertshaw
looks similar). This one has an assist heater as evident by the red and
yellow wires in the center. A normal control will not have these wires!
Another fan/limit unit is made by
Camstat and can have the added feature of an electric heater to cause the
fan to come on after a certain period of time even if the furnace hasn't
gotten hot enough. This feature is useful on furnaces that have high airflow
and would cause the control to cycle after the plenum has reached proper
temperature. Honeywell and White-Rodgers also makes one like this too.
Newer furnaces will have an electronic
control board to turn on the blower. This control can be part of the furnace
control board or a stand alone box made by one of the popular control manufactures
Honeywell, White-Rodgers, Fenwall, Johnson Controls, Robertshaw, Steveco
(White-Rodgers), Mars (General Electric), Penn-Baso (Johnson Controls).
Most all electronic fan controls have
adjustments to adjust how long the fan runs and how long it waits to turn
on the fan. This is usually a jumper wire that can be moved to stops marked
90, 120 320 ect. seconds of on time after the burner shuts off. The on
time is usually not adjustable. When one of these devices fail the only
repair is to replace it.
If you have central air conditioning
then you will have a relay added to turn on the blower. Most furnaces use
the lower speeds for heating and high speed for cooling. Older furnaces
will still use the limit control to turn the fan on low but switching
the setting on the thermostat switch from "auto" to "on" will override
the low speed and cause the blower to run on high. Most newer furnaces
have a central control board to change speeds.
Nuisance problems: The following are
problems that are more annoyances than functionality problems and should
be addressed as such: As a general rule it is ok for the fan to run if
it doesn't need to. It is not ok for the fan not to run if it should be
on.
-
Blower won't shut off. There are several reasons why the
fan won't shut off but rule #1: is unless you are sure what is wrong with
it, don't F--- with it until Monday morning when the supply houses are
open and you can get parts. Rule #2 if you are in airconditioning mode
see rule #1.
-
Blower comes on in high speed right away on your gas or oil
forced air furnace. This is caused by the "G" terminal on the thermostat
being activated most likely because it is an electric heat thermostat or
a dual mode thermostat set in electric heat mode. (see rule #1 above).
-
Blower comes on one more time after a heat call then shuts
off. Solution: raise the "ON" temperature on the control shown above.
If the control is being difficult to move see rule #1 above!
-
You have had some work done to your gas or oil furnace and
the air coming out is not as hot as it used to be. This is caused by the
fan having been moved to a higher speed for the heat mode. While the air
isn't as hot as it was before there is no down side to this other than
the mind-set that hotter is better. In fact the furnace will be more efficient.
But if you feel the need for hotter air move the fan to a lower speed.
See rule #1 above.
-
The blower shuts off at some time in the heat cycle but comes
back on again reliably. Lower the "Off" setting on the fan control. See
Above if it is a conventional control. Replace your
module if it is an electronic control (this is a problem that needs correcting).
-
You have a heat pump that uses a heat sequencer for the fan
control and it doesn't always come on. Replace the heat sequencer if it
is a week day, install a relay (if you have one) if it is a week end. (this
is a problem that needs correcting)
-
You have a Trane heat pump and the (honeywell) delay module
goes bad (Fan won't run). Rewire it so the Common and Green wires activate
the fan relay then decide what you will do with it once you get a price
for that OEM. module. (This is a problem that needs correcting). If fan
won't shut off read and heed rule #1 again.
I recommend the nationwide chains
Grainger
or Johnstone as a source
of parts. Written by Scott Meenen n3sjh.
 |
 |
Images of a thermodisk fan control
(limit controls look like this too) used on some furnaces where there is
not enough room for a probe type control.
Most older furnaces use a probe type control which is
shown below.
Note: Electric
furnace sequencers look somewhat like this
and clothes dryer thermostats and high limits are almost
identical.
Description of this control
 |
 |
Image of Camstat
(brand name) probe type fan control.
This control has an assist heater (top terminals) to
make the fan come on after a predetermined period of time with the gas
valve or oil burner.
This type of control is especially useful in a situation
where the furnace has plenty of air flow and would shut the control off
soon after the fan starts. Camstat makes a version that has no assist heater.
The settings on the dial is the temperature that the
control will shut off the fan.
Definitions:
-
Blower: usually a squirrel cage centrifugal air moving device. Will move
large volumes of air relatively quiet. Will use less energy with more back
pressure.
-
Fan: a paddle type air moving device used where noise is not a major consideration.
Will use more energy with more back pressure.
-
Combustion blower: A blower used on high efficiency gas furnaces or oil
burners to move combustion air. usually 1/20 to 1/6 horsepower.
-
OEM: Original equipment manufacturer.
-
Horsepower: 746 watts
-
RPM: revolutions per minute.
-
Service factor: the extent to which a motor can be safely overloaded beyond
its name plate ratting without over heating.
-
Air over horsepower: The rating of a motor assuming air flow through the
windings usually as a result of the air moving device.
-
SAE: Society of Automotive Engineers.
-
High efficiency furnace: Furnace that uses over 85% of the energy in the
gas.
-
Condensing furnace: Gas furnace that uses over 92% of the energy in the
gas and condenses the gas into liquid condensate and hot air. If your furnace
has PVC pipe venting it then you have a condensing furnace.
Related Pages:
Wiring
colors.
Fan
Motor Replacement.
Problem
solving.
FAQ.
More
F.A.Q.
More
definitions.
Gas
burner system page.
Oil
heat page.
Heat
pump repair page.
Heat
pump defrost cycle.
What
is a combustion blower motor system?
This page will be updated soon
Good Luck Scott
ITEMS
FOR SALE WITH PARTS ADDED SOON
We service and repair the following brands:
American Standard, Amana, Arco, Arco-Aire, Bryant, Carrier,
Coleman Evcon, Comfortmaker, Day/Night/Payne, Dunham-Bush, Fedders, Fredrich,
Goodman, General Electric, Hotpoint, Heil, Intertherm, Janitrol, Kenmore,
Lennox (Armstrong, Johnson Air-Ease), Miller, Modine, Nordyne, Rheem/Ruud,
Sears, Stewart Warner, Trane, Williams, White-Westinghouse, Whirlpool,
Weil Mclain,
York, (Frasier Johnson/Borg Warner Luxair) and others.
Written By: Scott
Meenen N3SJH of:
G&S MECHANICAL SERVICES.
Specializing in Mechanical, Controls
and Electrical Modifications Of
Heating, Air-conditioning, Refrigeration,
Cold storage,
Ice Production and Food preservation.
Anything having to do with Heat
and Energy.
Serving MD, DC, and Northern
VA.
Contact us 301-591-1646
Email
us at: jsmeenen@toad.net
This text written by: Scott Meenen * G & S Mechanical
Go to or return to the G&S
Mechanical home page.
For
a list of all files on this site go to the site map.