Top view of compressor motor starting capacitor that
blew its top off. This device is used in what is called a "hard start kit".
Every single phase air conditioning or refrigeration compressor should
have one. These devices are also used on high torque applications like
air compressors and pumps. If your system is tripping the circuit breaker
on a regular basis this repair should fix the problem. Please do not install
a larger breaker or fuse
to stop nuisance trips. If you have fuses in your outdoor disconnect and
they are causing you problems with blowing. I recommend replacing them
with copper tubing and installing the correct size circuit breaker (a 3
ton system can get away with a 20 amp breaker and 2 ton 15).
Notice the wires in the top right corner of the service cabinet. This box also has a 2 pole Honeywell contactor and Idec low voltage control relays. The relay in the center of the box is a GE MARS 165 potential relay that controls the starting function (a ge mars 66 and a 150MFD 330volt cap. will do most systems). It was ok untill recently even though this system stops and starts a lot, being on continuous pump down. I finally had to replace the relay and used a univeral electronic relay which I don't like, the mechanical relay worked so much better.
Any refrigeration system that uses a TEV (thermostatic expansion valve) instead of a capillary tube or orifice must have a start capacitor because the system pressure may not equalize for a period of time during the off cycle.
If you replace the indoor cooling coil with one that has a thermostatic expansion valve you may think that there is a problem with the compressor if it doesn't have one. A shorted start capacitor can cause the system to trip the circuit breaker.
Most of the so-called "solid state" start assist devices are garbage because they use thermistors instead of a relay, don't even bother to install them. Use a start relay and start capacitor like shown above. There are some two wire start assist devices that really do work such as "Kick Start" but they must connect the start capacitor directly to the circuit.
Ge/Trane/Manurope compressors generally don't need a hard start kit but it will still help. Most scroll compressors have no need for a start kit but they do need a anti-restart timer or they can run backwards.
Email us at: jsmeenen@toad.net
Specializing in Mechanical, Controls and
Electrical Modifications Of
Heating, Air conditioning, Refrigeration,
Cold storage,
Ice Production and Food preservation.
Anything having to do with Heat and Energy.
To
read about backup power systems using solar energy click here.
To
ask us to help solve a furnace problem use this form.
To
ask us to solve an air conditioning or heat pump problem use this form
To
see what kind of gas valve you have click here
To
read questions and answers click here
For more
airconditioning stuff
For a framed list
of all files go to the G&S mechanical home page:
For
a list of all files on this site go to the sitemap: